10.1.12 Priority switching
The solar circuit has priority for loading the
storage cylinder. If the temperature in the
solar circuit is too low or if the maximum
temperature of the storage cylinder is
reached, the system switches to the
swimming pool circuit/secondary circuit. An
increase in temperature of the collector is
monitored. If, within 5 minutes, the collector
temperature has risen by more than 1K, the
control unit shuts off the secondary loading
and blocks off the latter for a period of 4
minutes. During this period, the control unit
waits for the switch-on condition for the
priority loading. Once this period has
elapsed or if the control unit has reverted to
priority load status, the block against
secondary loading is lifted. After no longer
than one hour of swimming pool
heating/secondary storage cylinder heating,
this is interrupted and the switch-on
conditions for the priority storage cylinder
are checked for a period of 4 minutes.
10.1.13 Impulse-controlled circulation
The circulation pump can be controlled as
per demand. Shortly before hot water is
removed from the system, a request for
heat is sent to the control unit by means of
a button or by briefly opening the hot water
tap (min. 1 s). The circulation switch is used
to start the circulation pump for an
adjustable time. Once this active period has
elapsed, the pump is then blocked from
being reactivated for a certain (adjustable)
period.
10.1.14 Thermal
circulation
In the case of thermal circulation, the
potable water supply is held at a preset
minimum temperature (thermostatic
function) within two adjustable timeframes.
To prevent the pump from switching on and
off due to only minimal differences in
temperature, a hysteresis of 5K is preset.
10.1.15 Anti-Legionnaire’s disease function
A check is made at regular intervals (every
day, every week) as to whether the water in
the storage cylinder was at 60°C for at least
one hour in this period. If not, then between
16 and 18:00 hours, the system attempts to
heat the water in the storage cylinder to
65°C and to maintain it at a temperature of
60°C. If the water in the storage cylinder
does not reach this temperature within
these two hours or if, within the space of an
hour, the temperature falls again to below
60°C, an error is reported. However, the
control functions are retained. If the
temperature of 60°C was maintained for at
least one hour, the anti-Legionnaire’s
disease routine is reset and the monitoring
process starts from this time point. This
function is designed to prevent the growth
of legionella bacteria.