Installation and Operating Instructions
SDC 306 1316BED036-11B-E Date 06/09
- 22 -
9.2 “Program” menu
All changeable parameters can be checked
in this menu and changed if necessary.
Common values are set at the factory,
which will generally ensure that the system
functions correctly.
The number of displayed values depends
on the type of controller and the additional
functions set. Only the values required in
each case are displayed.
i
Only the configuration-specific symbols are displayed!
Parameters Value range Factory setting
Timeframe R2 start 0:00 – 23:59 7:00 – 22:00
Timeframe R2 stop 0:00 – 23:59 7:00 – 22:00
Timeframe R3 start 0:00 – 23:59 7:00 – 22:00
Timeframe R3 stop 0:00 – 23:59 7:00 – 22:00
Timeframe 1 circulation start 0:00 – 23:59 7:00 – 22:00
Timeframe 1 circulation stop 0:00 – 23:59 7:00 – 22:00
Timeframe 2 circulation start 0:00 – 23:59 7:00 – 22:00
Timeframe 2 circulation stop 0:00 – 23:59 7:00 – 22:00
Storage cylinder 1 maximum temperature 5°C – 95°C 8 5°C
Solar circuit Td start 3K – 20K 6K
Solar circuit Td stop 2K – 18K 3K
Storage cylinder 2 maximum temperature 5°C – 95°C 8 5°C
Maximum temperature of swimming pool 5°C – 50°C 25°C
Solar circuit 2 Td start 3K – 20K 6K
Solar circuit 2 Td stop 2K – 18K 3K
Start temperature, auxiliary heating 5°C – 90°C 60° C
Thermal switch-on threshold* 20°C – 55°C 40°C
Boiler Td start 3K – 20K 6K
Boiler Td stop 2K – 18K 3K
RLA/RLM Td start 3K – 20K 4K
RLA/RLM Td stop 2K – 18K 2K
Maximum temperature for transfer storage cylinder 20°C – 95°C 85°C
Transfer Td start 3K – 20K 6K
Transfer Td stop 2K – 18K 3K
Set the time 0:00 – 23:59 12:00
Maintenance (or summer/winter)** 0 – 1 0
* The thermal switching threshold is the temperature that is maintained in the pipes (as a
minimum). To prevent rapid switching on and off, a hysteresis of 5K is used.
** If maintenance is activated or if the system is set to winter (=1), the swimming pool will not
be heated (affects systems 10 and 11). If maintenance is deactivated or switched to summer
(=0), then loading takes place according to the primary/secondary principle.