PET-70216/ET-7026 User Manual, version 1.0.1 beta1, Page: 65
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]om
Step 5: Add a DI for reading PHS1 input
Set PHS1 to be an input, you can
using the Modbus Register 1,
then select Discrete Input as the
Register Type and type PHS as
the Alias.
Step 6: Save selected sensor settings
Click Save button to complete set up
Step 7: Add the register item for writing selected motor output to turn/
After save the register settings, the new register item will be displayed in the
Group table.
Click Edit in the second row of the Group table and then the Edit Group
Register window will be displayed.
Click Edit to edit the register item