Savin 4027 Especificaciones

Busca en linea o descarga Especificaciones para Multifuncionales Savin 4027. Savin 4027 Specifications Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 70
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
www.rosemount.com
Reference Manual
00809-0100-4027, Rev AA
December 2005
Rosemount 4500
Hygienic Pressure Transmitter
for Life Sciences Applications
74
Vista de pagina 0
1 2 3 4 5 6 ... 69 70

Indice de contenidos

Pagina 1 - Rosemount 4500

www.rosemount.comReference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500Hygienic Pressure Transmitter for Life Sciences Applications74

Pagina 2

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45002-2CONSIDERATIONSGeneral Measurement accuracy depends upon proper installation of th

Pagina 3 - Pressure Transmitter

Reference Manual 00809-0100-4027, Rev AADecember 20052-3Rosemount 4500Figure 2-2. HART Installation FlowchartSTART HEREBench Calibration?Field Install

Pagina 4

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45002-4INSTALLATION PROCEDURESFor dimensional drawing information refer to Appendix A: R

Pagina 5 - Table of Contents

Reference Manual 00809-0100-4027, Rev AADecember 20052-5Rosemount 4500NOTESensor burst pressure limits may be less than clamp pressure limits.NOTEMost

Pagina 6

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45002-6HART CommunicatorUsage NoteThe HART Communicator can be used to configure the sec

Pagina 7 - Section 1 Introduction

Reference Manual 00809-0100-4027, Rev AADecember 20052-7Rosemount 4500Connect Wiring and Power UpWiring for HART Protocol NOTEUse shielded twisted pai

Pagina 8

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45002-8Grounding Transmitter CaseAlways ground the transmitter case in accordance with

Pagina 9 - Section 2 Installation

Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comSection 3 ConfigurationCommissioning on the bench With HART . . .

Pagina 10

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-2COMMISSIONING ON THE BENCH WITH HARTCommissioning consists of testing the transmi

Pagina 11

Reference Manual 00809-0100-4027, Rev AADecember 20053-3Rosemount 4500Wiring Diagrams Bench Hook-upConnect the bench equipment as shown in Figure 3-1

Pagina 13

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-4HART COMMUNICATORMenu Tree1. Universal. Rev.2. Field. Dev. Rev.3. Software Rev1.

Pagina 14

Reference Manual 00809-0100-4027, Rev AADecember 20053-5Rosemount 4500Fast Key Sequence The following menu indicates fast key sequences for common fun

Pagina 15

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-6Review Configuration DataNOTEInformation and procedures in this section that make

Pagina 16

Reference Manual 00809-0100-4027, Rev AADecember 20053-7Rosemount 4500CHECK OUTPUT Before performing other transmitter on-line operations, review the

Pagina 17 - Section 3 Configuration

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-8BASIC SETUPSet Process Variable UnitsThe PV Unit command sets the process variabl

Pagina 18

Reference Manual 00809-0100-4027, Rev AADecember 20053-9Rosemount 4500Rerange with a HART Communicator OnlyThe easiest way to rerange is to use the HA

Pagina 19

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-10Rerange with AMS onlyRight click on the device and select “Configuration Propert

Pagina 20

Reference Manual 00809-0100-4027, Rev AADecember 20053-11Rosemount 4500LCD Display ConfigurationThe Meter Options command customizes the LCD display.

Pagina 21

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-12Table 3-1. Rosemount (Standard) Alarm and Saturation ValuesTable 3-2. NAMUR-Co

Pagina 22

Reference Manual 00809-0100-4027, Rev AADecember 20053-13Rosemount 4500AMSRight click on the device, select “Device Configuration”, then select “Alarm

Pagina 23

Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comRosemount 4500 Hygienic Pressure Transmitter . . . .NOTICERead thi

Pagina 24

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-14Alarm Level Verification If the transmitter electronics board, Transmitter, or L

Pagina 25

Reference Manual 00809-0100-4027, Rev AADecember 20053-15Rosemount 4500Scaled Variable ConfigurationThe scaled variable configuration allows the user

Pagina 26

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-16HART CommunicatorTo configure the scaled variable with a HART Communicator, perf

Pagina 27

Reference Manual 00809-0100-4027, Rev AADecember 20053-17Rosemount 4500AMS Right click on the device and select “Device Configuration” then select “SV

Pagina 28

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-18AMS Right click on the device and select “Device Configuration,” then “Re-mappin

Pagina 29

Reference Manual 00809-0100-4027, Rev AADecember 20053-19Rosemount 4500Loop Test The Loop Test command verifies the output of the transmitter, the int

Pagina 30

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-20AMSRight click on the device and select “Diagnostics and Test,” then “Loop test”

Pagina 31

Reference Manual 00809-0100-4027, Rev AADecember 20053-21Rosemount 45004. Select the back arrow from the HOME/ONLINE screen. The HART Communicator men

Pagina 32

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-22AMS Applying a User ConfigurationAny amount of user configurations can be create

Pagina 33

Reference Manual 00809-0100-4027, Rev AADecember 20053-23Rosemount 4500AMSRight click on the device and select “Configuration Properties” from the men

Pagina 35

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45003-24The 4500 is set to address zero (0) at the factory, which allows operation in th

Pagina 36

Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comSection 4 Operation and MaintenanceCalibration for HART Protocol

Pagina 37

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45004-2Table 4-1. Recommended Calibration TasksNOTE:The transmitter performs to specifi

Pagina 38

Reference Manual 00809-0100-4027, Rev AADecember 20054-3Rosemount 4500Figure 4-1 also identifies the approximate transmitter location for each calibra

Pagina 39

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45004-4Determining Calibration FrequencyCalibration frequency can vary greatly depending

Pagina 40

Reference Manual 00809-0100-4027, Rev AADecember 20054-5Rosemount 4500Choosing a Trim ProcedureTo decide which trim procedure to use, you must first d

Pagina 41

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45004-6Zero Trim NOTEThe transmitter must be within three percent of true zero (zero-bas

Pagina 42

Reference Manual 00809-0100-4027, Rev AADecember 20054-7Rosemount 4500NOTESelect pressure input values so that low and high values are equal to or out

Pagina 43

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45004-8Recall Factory Trim—Analog OutputThis command resets the transmitter analog outpu

Pagina 44

Reference Manual 00809-0100-4027, Rev AADecember 20054-9Rosemount 4500AMSRight click on the device and select “Calibrate,” then “D/A Trim” from the me

Pagina 45

Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comTable of ContentsSECTION 1IntroductionUsing This Manual . . . . .

Pagina 46

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45004-10a. If Yes is selected, proceed to Step 10.b. If No is selected, repeat Step 8.10

Pagina 47

Reference Manual 00809-0100-4027, Rev AADecember 20054-11Rosemount 4500NONPV LIMITA secondary variable read by the transmitter is outside of the trans

Pagina 48

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45004-12SPAN FAILThe span value, set with the local span adjustment button, exceeds the

Pagina 49

Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comSection 5 Troubleshooting OVERVIEW Table 5-1 provides summarized m

Pagina 50

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45005-2Table 5-1. Rosemount 4500troubleshooting tableSymptom Corrective ActionsTransmit

Pagina 51

Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comAppendix A Reference DataSpecifications . . . . . . . . . . . . .

Pagina 52

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-2Range and Sensor LimitsFunctional SpecificationsDynamic Performance250 millisecon

Pagina 53 - Section 5 Troubleshooting

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-3Overpressure LimitsTransmitters withstand the following pressure without damage:

Pagina 54

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-4Alarm ConfigurationRosemountHigh Alarm: ≥ 21.75 mALow Alarm: ≤ 3.75 mACustom Leve

Pagina 55 - Appendix A Reference Data

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-5DIMENSIONAL DRAWINGSFIGURE 1. Dimensional Drawings for the Rosemount 4500 Hygieni

Pagina 56

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500TOC-2Scaled Variable Configuration . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 57

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-6FIGURE 2. Dimensional Drawings for the Rosemount 4500 Hygienic Pressure Transmitt

Pagina 58

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-7FIGURE 3. Dimensional Drawings for the Rosemount 4500 Hygienic Pressure Transmitt

Pagina 59

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500A-8ORDERING INFORMATION Model Transmitter Type4500 Hygienic Pressure TransmitterCod

Pagina 60

Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comAppendix B Product CertificatesApproved Manufacturing Locations .

Pagina 61

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500B-2HAZARDOUS LOCATIONS CERTIFICATIONSNorth American CertificationsFactory Mutual (FM

Pagina 62

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500B-3N1 ATEX Type n (Pending)Certificate No. Baseefa05ATEX0092XATEX Marking: II 3 G E

Pagina 63

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 4500B-4

Pagina 64

Reference Manual 00809-0100-4027, Rev AA12/5/05Rosemount 4500www.rosemount.comIndexAAddressChanging . . . . . . . . . . . . . 3-24Alarm . . . . . .

Pagina 65

Reference Manual00809-0100-4027, Rev AA12/5/05Rosemount 4500Index-2PPower supplyHART protocol . . . . . . . . . . 2-7Power up . . . . . . . . . . . .

Pagina 67

Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comSection 1 IntroductionUsing This Manual . . . . . . . . . . . .

Pagina 68

Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500Emerson Process Management© 2005 Rosemount Inc. All rights reserved.¢00809-0100-402

Pagina 69

Reference Manual00809-0100-4027, Rev AADecember 2005Rosemount 45001-2SERVICE SUPPORT To expedite the return process outside of the United States, cont

Pagina 70 - ¢00809-0100-4027 ¤

Reference Manual 00809-0100-4027, Rev AADecember 2005Rosemount 4500www.rosemount.comSection 2 InstallationConsiderations . . . . . . . . . . . . . .

Comentarios a estos manuales

Sin comentarios